160kW Temporary Chiller Hire
Heat exchanger
Air Handling Unit (AHU) used with Chiller
160kW Temporary Chiller Hire
Heat exchanger
Air Handling Unit (AHU) used with Chiller

125a 3ph 5pin plug

160kW Packaged Chiller Hire

Weight

1260kg

Dimensions (LxWxH)

3355mm x 1105mm x 2205mm

  • Planned or Emergency Hire
  • 24/7/365 Support
  • Rapid Response
  • Nationwide Delivery
  • Air Handling Units Available
  • Heat Exchangers Available
  • Large Stock
  • Free Site Survey Available
Request Chiller Specifications

Chiller description

Our 160kW packaged chiller is aircooled with scroll compressors and coaxial evaporator. It also has a large shell & tube evaporator and 400 litre tank and a built in option for a high-pressure pump.

The integral manual bypasses, helps with ease of commissioning. All of our chillers have a Y-strainer which protects each unit and your process from failing.

Our 160kW chiller is an entirely packaged unit which can be modified for non-ferrous applications. The controls are very simple, making set up quick & easy. Vented or pressurised option as standard – no modifications are necessary.

If you choose not to use the internal pump there is a dedicated feed on the evaporator to run a high-pressure pump, entirely excluding the internal pump.

The 160kW chiller is available to hire for planned or emergency requirements, 24/7. Call our team today for an instant quote.

Request chiller

0800 464 7025

Available 24/7

Chiller Hire Process

What our customers say

Specifications

Cooling capacity (kW)
159

Design Conditions (°C)
Ambient: 30 / Entering: 12/ Leaving: 7

E.E.R (kW/kW)
3.39

Refrigerant Gas (R)
410A

Compressor Type
Scroll

Number of Compressors (N°)
4

Number of Circuits
2

Total Compressors Nominal Absorbed Power (kW)
41.04

Total Compressor Running Current (RLA) (A)
71.45

Capacity Steps (N°)
4

Type of Evaporator
Shell and Tube

Nominal Flow Rate (m3/h)
27.27

Pressure Drops (kPa)
60.31

Incoming Pressure PRV
3bar

System Volume
410L

Expansion Vessel Volume (Litres)
390

Hydraulic Connections
4” Bauer

Integral P3 Pump Included
Yes

Optional P5 Pump
Electrical Feed Included

Number of Condenser Coils (N°)
1

Number of Fans (N°)
3

Total Air Flow (m3/h)
57000

Nominal Absorbed Power (kW)
51.42

Maximum Absorbed Current (FLA) (A)
117.45

Maximum Starting Current (LRA) (A)
232.95

Plug type
125a 3ph 5pin plug

Electrical feed (V/ph/Hz)
400/3/50 + E (No Neutral)

Length (mm)
3355

Width (mm)
1105

Height (mm)
2205

Empty Weight (kg)
1260

Industry sectors

Take a look at the sectors that use this capacity chiller

Leisure & Tourism

Learn More

Facilities Management

Learn More

Education

Learn More
Planned Chiller Hire
Planned Chiller Hire

Are you working on a project that requires chillers? Arrange your free, comprehensive site survey and estimate today.

Emergency Chiller Hire
Emergency Chiller Hire

Do you need urgent chiller requirements to your building? We can be onsite within hours of receiving your call.

Call today for Emergency Chiller Hire 0800 464 7025

Available 24/7

  • FEBE 2024
  • ISO-9001 Certified Logo
  • OFTEC Accredited Logo
  • CHAS Accredited Logo
  • Constructionline Gold Logo
  • GAS Safe Logo
  • SSIP Logo
  • F-Gass Certified
  • SafeContractor Logo